EN RU
LVWave · Independent educational reference

Fire Detector Atlas

Educational reference based on NFPA 72 (2022 reference edition, incl. TIA 22-4), NFPA 90A, product listings and manufacturer documentation. Requirements vary by adopted code edition, AHJ, application and listed equipment. Verify the requirements applicable to each project. Not an NFPA, UL or AHJ publication or code interpretation.

CODENFPA 72 requirement CH. 29household (dwellings, Ch. 29) requirement ANNEXexplanatory, not mandatory NFPA 90AHVAC standard LISTING / MFRlisting or manufacturer instructions EXAMPLEillustrative value PHYSICSphysical principle
00

Spot-type spacing geometry

The S / S/2 / 0.7S geometry appears in several detector-spacing applications, but the value of S and additional installation requirements depend on detector type, listing and application.

S = 30 ft ≤ 15 ft 0.7 S ≈ 21 ft ≤ S/2
Plan view, smoke detectors, smooth ceiling. S/2 is measured at right angles from walls or partitions extending to within the top 15 % of the ceiling height.
30ftnominal spot smoke spacing, smooth ceiling, absent performance-based designCODE17.7.4.2.3.1
S/2max from walls/partitions to a smoke detector (15 ft at S = 30 ft)CODE17.7.4.2.3.1
0.7Salternative: every ceiling point within 0.7 S (≈ 21 ft at S = 30 ft)CODE17.7.4.2.3.1
40.8ftderived geometry for a 10 ft corridor: 2·√(21² − 5²). Not a prescribed spacing.EXAMPLE
32–100 °F · ≤ 93 % RH · ≤ 300 ft/minenvironmental limits for smoke detectors unless the detector is specifically designed/listed for other conditionsCODE17.7 LISTING / MFR
≤ 36 in Peaked row near the peak Beams / joists depth sets spacing gap High ceiling smoke stratification
Conceptual. Peaked/sloped, beam and high-ceiling rules differ for smoke and heat detectors — see the detector sections.

Why “≤ S/2 from the wall”?

S = 30 ft 15 ft 15 ft ≤ 15 ft 15 ft mirror weakest point between two detectors point at the wall same distance → same coverage
Section along the ceiling, smoke detectors. The wall acts like a mirror: a detector S/2 from the wall covers the wall zone the same way two detectors cover their midpoint.
  • Maximum, not target. For spot smoke detectors the Code sets the S/2 maximum; closer placement follows the manufacturer's instructions. Heat detectors have their own rule: on the ceiling ≥ 4 in from the sidewall (see 07).
  • How to measure. At right angles from walls or partitions extending to within the top 15 % of the ceiling height, to the detector center. Check every wall.
  • HEAT DETECTOR EXAMPLE. Adjust S first, then halve: 50 ft listed spacing on a 19 ft ceiling → 50 × 0.64 = 32 ft → ≤ 16 ft to the wall.
  • S/2 is the simple rule. The 0.7 S alternative (every ceiling point within 0.7 S) can allow more than S/2 along a narrow room. The corridor numbers below are derived geometry, not prescribed spacings.

Check a room EXAMPLE


Smooth flat ceiling, geometry only. 30 ft = nominal smoke spacing; for heat use listed spacing × height factor.
Detectors are spread evenly: equal gaps, half a gap to each wall.
01

Ionization smoke detector

Tends to respond more readily to the smaller combustion particles commonly produced by fast-flaming fires · NFPA 72 17.7 · UL 268 (system detectors) / UL 217 (smoke alarms)

≤ 12 in to top of detector ≤ 15 ft (S/2) supply diffuser keep out of direct airflow household (Ch. 29): ≥ 36 in from supply registers
Section — shared by spot smoke types 01, 02, 03 (when used as a smoke detector).
30ftnominal spacing, smooth ceilingCODE17.7.4.2.3.1
≤ 12insidewall mount: top of detector below ceilingCODE17.7.4.2.1
Airflowavoid direct HVAC airflow; account for air movement per the Code and manufacturer instructionsCODE17.7 LISTING / MFR
36inhousehold: from forced-air supply registers (and outside their direct airflow); from ceiling-fan blade tips (unless room configuration prevents); from door of bathroom with tub/shower (unless listed for such proximity)CH. 2929.11.3.4
Light fixturesseparation from fixtures (especially where fluorescent/electrical interference is a concern) — per manufacturer instructions; no universal NFPA distanceLISTING / MFR
+ Am-241 α +++ smoke particles I↓

How it alarms

  1. Am-241 ionizes air in the chamber
  2. Small current flows between plates
  3. Smoke particles attach to ions, current drops
  4. Change past the alarm threshold — alarm

Common components

Am-241 sourcesmall sealed source
Sensing chamberopen to smoke
Reference chambercompensation (many designs)
Measuring electronicsdesign-specific
Avoid household cooking zones — see Ch. 29 diagram direct HVAC airflow exhaust fumes, dust outside listed environmental range
02

Photoelectric smoke detector

Generally more responsive to the larger smoke particles commonly associated with smoldering fires · NFPA 72 17.7 · UL 268 / UL 217

30ftnominal spacing, smooth ceilingCODE17.7.4.2.3.1
≤ 15ftto walls/partitions (S/2)CODE17.7.4.2.3.1
Airflowavoid direct HVAC airflow; per Code and manufacturer instructionsCODE17.7 LISTING / MFR
36inhousehold: supply registers, ceiling-fan blade tips, bathroom door — same conditions as 01CH. 2929.11.3.4
LED light trap photodiode particle

How it alarms (light scattering)

  1. Light source pulses past the receiver
  2. Smoke scatters the light
  3. Scattered light reaches the receiver
  4. Signal past the alarm threshold — alarm

Common components (design examples)

Light sourcetypically LED; wavelength and number of optical channels are model-specific
Photodiodeoff-axis receiver
Optical chamber / labyrinthadmits smoke, blocks ambient light
Insect screenmany designs
Processordrift compensation on many models
Avoid household cooking zones — see Ch. 29 diagram steam, showers aerosols, dust air velocity above the listed limit
03

Multi-sensor / multi-criteria detector

Combines two or more sensing technologies. Sensor combinations and alarm algorithms are model-specific.

Per listingspacing and use follow the detector listing, the detection function relied on, NFPA application requirements and manufacturer instructions. Individual sensor channels do not automatically receive independent spacing credit.CODE17.7 / 17.6 LISTING / MFR
2+sensing technologies combinedLISTING / MFR
COCO sensor service life — model-specificLISTING / MFR
EXAMPLE ARCHITECTURE optical (smoke) thermal CO (some models) algorithm listed !

Logic EXAMPLE

  1. Smoke signal alone: evaluated with more caution
  2. Smoke + supporting signal (e.g., heat or CO): confirmation
  3. Faster alarm decision

EXAMPLEConceptual example — actual decision algorithms are manufacturer- and listing-specific.

Common components / example architecture

Optical smoke sensingcommon
Thermal sensingcommon
CO sensingsome models
Processorlisted algorithm
04

Projected-beam smoke detector

Detects smoke along a light path across the space: atriums, warehouses, plants · NFPA 72 17.7.4.7 · installed per manufacturer's published instructions

≤ 60 ftANNEX ≈ ½ spacingANNEX beam length — per listing TxRx
Plan view, smooth ceiling, end-to-end units. Spacing values are Annex guidance; actual layout follows the listing, manufacturer instructions, ceiling conditions, airflow and performance objective.
≤ 60ftsmooth-ceiling guidance between parallel beamsANNEXA.17.7.4.7
≤ 30ft≈ one-half of the selected beam spacing to a parallel sidewallANNEXA.17.7.4.7
Beam lengthmaximum per equipment listing — must not be exceededCODE17.7.4.7 LISTING / MFR
Sensitivityobscuration settings — per listing and manufacturerLISTING / MFR
Stable mountingdetector and reflector on stable surfaces — building movement can misalign the beamCODE17.7.4.7 LISTING / MFR
End-to-end transmitter receiver Single-ended / reflective Tx/Rx prism reflector

How it alarms

  1. Light beam to the receiver (end-to-end) or to a reflector and back (single-ended)
  2. Smoke along the path reduces the received signal
  3. Reduction reaches the listed alarm setting — alarm
  4. Sudden total blockage — typically a trouble signal (listed detector behavior)

Common components

End-to-endseparate transmitter + receiver
Single-endedcombined transceiver + prism reflector
Alignment aidssome models: automatic alignment
Avoid cranes, racks, signage in the beam path strong light into the receiver unstable / flexing mounting surfaces
05

Air-sampling smoke detector (ASD)

A pipe network with sampling ports draws air to a central detector · NFPA 72 17.7.4.6

detector ≤ 30 ftEXAMPLE ≤ S/2 ≤ 120 s from the farthest port
Section. Port spacing shown is a prescriptive smooth-ceiling example, not an inherent ASD specification.
≤ 120smaximum sample transport time from the farthest sampling port to the detectorCODE17.7.4.6.2.1
Port = spotin the absence of specific performance-based design criteria, each sampling port is treated as a spot-type smoke detector for location and spacingCODE17.7.4.6
Sensitivitydetector- and application-specificLISTING / MFR
Port sizesize and quantity from the listed pipe-network design calculations/software and manufacturer instructionsLISTING / MFR
air samples filter optical fan flowmonitor

How it alarms

  1. Aspirator draws air through the ports
  2. Filtering, where used
  3. Optical sensing chamber measures smoke
  4. Multiple programmable alarm thresholds may be available depending on the listed detector

EXAMPLESome VESDA/Xtralis systems use Alert, Action, Fire 1 and Fire 2.

Common components

Aspiratorfan
Optical sensing chambersensing technology varies by product
Filterwhere used
Airflow monitoringblocked or broken pipe
Pipe networkpressure, airflow, transport time and sampling-point performance are calculated with the listed design method/software
06

Duct smoke detector

Smoke detection for control of smoke spread in HVAC systems · NFPA 72 17.7.6 (location/installation 17.7.6.5) · where required by NFPA 90A. Duct smoke detection is not a substitute for required open-area detection.

filter straight run from elbow — MFR guidance (e.g. ≥ 6 duct widths) detector
Supply side example: downstream of filters (NFPA 90A). Follow the detector's listed installation instructions and verify proper sampling airflow.
> 2,000cfmsupply systems: detector downstream of air filters and ahead of any branch connectionsNFPA 90A6.4.2.1
> 15,000cfmreturn systems serving more than one story: at each story, before connection to the common return and before any recirculation or fresh-air inlet connection. Exceptions exist — check the adopted NFPA 90A / code for the specific system.NFPA 90A6.4.2.1
Representative sampleinstalled to obtain a representative sample of the airstreamCODE17.7.6.5
≥ 6 widthstypical manufacturer/application guidance for avoiding turbulent locations (elbows, dampers)LISTING / MFR

Remote indicator

Provides indication for a detector whose status or location is otherwise not readily identifiable — where required, subject to system/code configuration.

Remote test station

A separate testing accessory/capability. Its use depends on the detector/system, manufacturer and project requirements. Not interchangeable with a remote indicator.

airflow SD sampling tube exhaust
Tube sizing and orientation depend on the listing, manufacturer and system design.

How it works

  1. Sampling tube in the duct picks up a sample
  2. Duct pressure differential drives it through the sensing chamber
  3. Smoke detected → HVAC / fire-alarm control sequence

Common functions can include fan shutdown and/or damper operation. Engineered smoke-control sequences can operate differently.

Avoid turbulent locations right after elbows or dampers air velocity outside the listed range humidifier discharge
07

Spot-type heat detector

Fixed-temperature, rate-of-rise or rate-compensated operation · NFPA 72 17.6 · UL 521

4–12 in sidewall, below ceiling ≥ 4 in · ≤ S/2 ceiling mount, from sidewall > 4 in ≤ ⅔ S beams > 18 in deep, > 8 ft o.c.: each bay treated separately
Section. S = listed spacing (UL 521).
Slisted spacing — e.g. 25, 30 or 50 ft (examples, not a complete set)CODE17.6.3 EXAMPLE
≥ 4 in · 4–12 inceiling: ≥ 4 in from sidewall; sidewall: 4–12 in below ceilingCODE17.6.3.1.3.1
½ Sperpendicular to solid joistsCODE17.6.3
⅔ Sperpendicular to beams more than 4 in deepCODE17.6.3
+20°Frating at least 20 °F above the maximum expected ceiling temperatureCODE17.6.2.3
0.4× Hhigh-ceiling reduction need not result in spacing below 0.4 × ceiling heightCODE17.6.3.5.2–17.6.3.5.4
Spacing multiplier, ceilings 10–30 ft 00.51.0 1.000.910.840.770.710.640.580.520.460.400.34 ≤1012141618202224262830 ceiling height up to, ft · CODE Table 17.6.3.5.1
EXAMPLE 50 ft listing, 19 ft ceiling → 50 × 0.64 = 32 ft. Above 30 ft the table gives no prescriptive multiplier: use the appropriate listing, manufacturer, performance-based/engineered and AHJ-approved approach.
Temperature classification ClassColorRating °FMax °F 0200400600 Low Ordinary Intermediate High Extra high Very extra high Ultra high none none white blue red green orange 100–134135–174175–249250–324325–399400–499500–575 80115155230305380480 bar = rating · blue tick = max ceiling temp · CODE Table 17.6.2.1
68104140176 0246810 min°F 135 °F fixed rate-of-rise EXAMPLE
EXAMPLE 135 °F is a common fixed rating, not the only one; 15 °F/min is a typical rate-of-rise example. Actual operating characteristics per listing/manufacturer.

Operating modes

  1. Fixed temperature: element reaches its rating
  2. Rate-of-rise: temperature rises faster than the listed rate (typical example 15 °F/min)
  3. Rate-compensated: accounts for thermal lag

Common sensing technologies

Thermistorelectronic / addressable models
Bimetaloften self-restoring
Eutectic elementnon-restorable
Pneumatic rate-of-riseair chamber with vent

A given detector uses one or more of these — not all of them.

08

Linear / line-type heat detector

Heat sensing along a cable or tube: cable trays, conveyors, tunnels, parking garages · NFPA 72 17.6

≤ 20 in ≤ S/2 S cable tray sine-wave run (MFR)
Section. Special applications (trays, conveyors, tanks) — per manufacturer's layout.
≤ 20inon the ceiling or on the sidewall not more than 20 in below the ceilingCODE17.6.3.1.3.2
S · S/2S per listing; S/2 wall-spacing concept where applicableCODE17.6.3 LISTING / MFR
Alarm temp.alarm temperature / operating range — per product listingLISTING / MFR
High ceilings: exceptionTable 17.6.3.5.1 derating does not apply in the same way to line-type electrical-conductivity detectors and pneumatic rate-of-rise tubing, which rely on integration effect — manufacturer's published instructions govern alarm point and spacing.CODE17.6.3.5.2–17.6.3.5.4 LISTING / MFR
normal at rating conductors contact
Digital fixed-temperature electrical-conductivity cable only.

How digital fixed-temperature LHD works

  1. Two conductors separated by heat-sensitive polymer
  2. Polymer yields at the rated temperature
  3. Conductors contact — alarm; compatible interface/location equipment can identify the distance to the actuated point

Types — different mechanisms

Digital / electrical-conductivityheat-sensitive cable; operating principle depends on product
Analogtemperature-dependent electrical characteristics monitored along the cable
Fiber-optic DTSdistributed optical temperature measurement along fiber
Avoid tension, sharp bends crushing by fasteners unlisted splices
09

Flame / radiant-energy fire detector

Placement is not based on a universal spacing grid · NFPA 72 17.8

Placement is performance-based CODE 17.8

expected fire size
fuel
detector sensitivity / listing
field of view
distance
atmospheric attenuation
interfering radiation
obstruction / line of sight
purpose of detection
required response

Every area requiring detection must be within the field of view of a detector, without obstruction.

d · 100 %2d · ≈ 25 % field of view — per listing shadow
PHYSICS Idealized inverse-square explanation. Actual detection distance also depends on fuel, flame size, atmosphere, viewing angle and detector listing.
1/d²received radiant energy decreases approximately with the inverse square of distancePHYSICS
FOVfield of view — per detector listing (example: many products ≈ 90°)LISTING / MFR EXAMPLE
≈ 4.3–4.5 µmimportant CO₂ emission region used by many hydrocarbon IR flame detectorsPHYSICS
Line of sightclear line of sight required to the protected areaCODE17.8
UV185–260 nmEXAMPLE visible CO₂ ≈ 4.3–4.5 µmIR schematic spectrum, not to scale

Technologies

  1. UV: senses ultraviolet radiation (typical product band shown as example)
  2. IR / multispectrum: many analyze temporal flame/flicker characteristics to distinguish flame from steady background radiation
  3. Multi-channel detectors correlate two or more spectral signals; exact alarm logic is manufacturer- and listing-specific

Common components — technology dependent

UV sensorUV-type detectors
IR sensor(s) + filtersIR / multi-IR types
Optical windowmust stay clean
Optical self-checksome models
Signal processorlisted algorithm
Potential interference / nuisance sources welding lightning strong / hot radiation sources reflected radiation other UV/IR interference
Optical obstruction / loss of sensitivity dust grease / oil paint water / ice physical obstruction
10

Manual fire alarm box (pull station)

Where manual fire alarm boxes are required by the applicable code or system design, NFPA 72 governs their installation and location · NFPA 72 17.15

EXIT ≤ 5 ft 42–48 in finished floor → operable part to the nearest box ≤ 200 ft travel
Wall elevation at an exit doorway.
42–48infinished floor to operable partCODE17.15.6
≤ 5ftfrom each exit doorway on each floorCODE17.15.9.4
≤ 200fthorizontal travel distance to the nearest box on the same floorCODE17.15.9.5
> 40ftgrouped openings wider than 40 ft: a box on both sides, within 5 ft of each sideCODE17.15.9.6
Visibleconspicuous, unobstructed, accessibleCODE17.15.9.2
Rednormally red unless the installation environment precludes redCODE17.15.9.3
FIRE PULL contact FACP

How it works CODE 17.15.7

  1. Single-action: one motion. Double-action: two separate motions
  2. Mechanism latches, contact/electronics change state
  3. Alarm at the control unit · reset per product design

Common construction examples

Operating mechanismmechanical
Electrical contact / switchdesign-specific
Addressable electronicson applicable products
Reset mechanismdesign-specific

CODE 17.15.8 · Optional accessory: a listed protective cover is permitted over single- or double-action boxes as applicable.

Clearance summary

Show table for all types
TypeSpacingWallsMountingOther
Spot smoke (01–02) 30 ft CODE≤ S/2 CODEsidewall: top ≤ 12 in below ceiling CODE direct airflow: avoid CODELISTING / MFR · 36 in registers / fan / bath door CH. 29 · cooking: 10 ft exclusion, 6–10 ft exception, 10–20 ft listed CH. 29 · light fixtures LISTING / MFR
Multi-sensorper listing & function LISTING / MFRno automatic per-channel credit
Projected beam≤ 60 ft ANNEX≈ ½ spacing (≤ 30 ft) ANNEXper listing; stable surfaces LISTING / MFRbeam length ≤ listed max CODE
Air samplingport = spot detector CODE≤ S/2 EXAMPLEtransport ≤ 120 s CODE · port size per listed design LISTING / MFR
Ductrepresentative airstream sample CODEsupply > 2,000 cfm: after filters, before branches; return > 15,000 cfm, multi-story: each story NFPA 90A · ≥ 6 widths from elbow LISTING / MFR
Spot heatlisted S × height factor (10–30 ft) CODE≤ S/2 · ≥ 4 in CODEsidewall 4–12 in below ceiling CODErating ≥ max ceiling temp + 20 °F; ≥ 0.4 × H floor on reduction CODE
Line-type heatper listing LISTING / MFR≤ S/2 CODEsidewall ≤ 20 in below ceiling CODEhigh-ceiling derating exception for integration-effect types CODE
Flameperformance-based CODEclear line of sight; FOV per listing CODELISTING / MFR
Pull stationtravel ≤ 200 ft CODE≤ 5 ft from exit doorway CODE42–48 in CODEopenings > 40 ft: both sides CODE
Fire Detector Atlas · LVWave independent educational reference. References: NFPA 72 (2022 reference edition) Chapters 17 and 29 with TIA 22-4; NFPA 90A; UL 217 / 268 / 521; manufacturer documentation. Original diagrams and paraphrased explanations — not reproduced from NFPA. Not an NFPA, UL or AHJ publication. Verify requirements for each project against the adopted code edition, the AHJ and listed equipment instructions.
Call Now Free Quote